![Jung Smart Control SC 1000 KNX Скачать руководство пользователя страница 225](http://html1.mh-extra.com/html/jung/smart-control-sc-1000-knx/smart-control-sc-1000-knx_product-documentation_2031686225.webp)
Art. No. SC 1000 KNX
The indoor temperature, and optionally the outdoor temperature, is displayed in the top third of
the display.
The available parameters for the room temperature controller page can be used to decide which
of the three available channel functions on the room temperature controller page can be
displayed and operated. The functions on this page are always operated using the selection
operation and rocker function. The sequence, in which the three functions are displayed on the
room temperature controller page, cannot be changed. At the top, the "Operating mode
switchover", if available, is displayed, followed by the "Setpoint shift" function. The room
temperature controller page is completed in the bottom third with the channel function "Fan
controller" (figure 107). If, for example, the operating mode switchover was not enabled, the
setpoint shift is displayed above the fan control. At the same time, the size of the display and
operating elements is adapted dynamically to two elements.
In addition, it is possible to specify in the "Room temperature controller page" parameter node
whether a status text is to be displayed for the three functions.
It is only possible to enable a presence button in the parameters of the room temperature
controller page for the "Operating mode switchover" channel function. In contrast to the
operation of the channel function on the Start or Favourites page, this is not selected by
operating the sensor areas
Z
and
^
, but can be operated directly in a separate part of the
display and operating element of the function of the room temperature controller page. A
comfort extension is activated by operating the presence button icon (see page 110), if the
presence button for presence recording was set in the "Controller functionality" parameter node
and if night operation or frost/heat protection is activated. If no presence button is
parameterised, the icon is shown in darkened form and is not sensitive.
The special feature on the room temperature controller page is that the remaining time of the
comfort extension is displayed, accurate to one minute.
Even on this special page, the operating mode is switched over using the sensor surfaces of the
rocker function. When the required operating mode is selected, the currently selected mode is
shown in a recessed box and confirmed by displaying the status text.
In the parameters of the room temperature controller page, the display of the icon (figure 47)
can only be permitted for the "Setpoint shift, internal" channel function. The function is operated
in the same manner. In addition, in these parameters it is possible to assign a designation for
the "Setpoint shift" function, which is then displayed on the room temperature controller page.
i
The absolute setpoint temperature is visualised on the setpoint shift display element. The
parameter "Display of the inside temperature" in the node "display" of the PlugIn
determines whether the absolute setpoint temperature is displayed in °C or °F. If this is
configured to "no display", the absolute setpoint temperature is displayed in °C.
A designation of max. 18 characters can be assigned to the "Fan controller, internal" channel
function, which is then shown on the room temperature controller page.
Page 225 of 347
Software "Smart Control 501511"
Functional description