Art. No. SC 1000 KNX
cycle time by this parameter In the "0"
setting, the setpoint temperature is not
transmitted automatically cyclically.
Upward adjustment of
the basic setpoint
temperature
(0...10) * 1 K
+ 2 K
This is used to show the maximum
range in which the basic setpoint
temperature can be adjusted upwards.
This parameter cannot be changed!
Downward adjustment
of the basic setpoint
temperature
(-10...0) * 1 K
- 2 K
This is used to show the maximum
range in which the basic setpoint
temperature can be adjusted
downwards. This parameter cannot be
changed!
Step width of the
4-level setpoint shift
0.5 K
This parameter defines the value of a
level of the basic setpoint shift. The
basic setpoint can be shifted by up to 4
levels. The parameter cannot be
changed!
Lower the setpoint
temperature during
standby operating mode
(heating)
(-128...0) * 0.1 K
-128...
-20
...0
The value by which the standby setpoint
temperature for heating is lowered
compared to the heating comfort
temperature.
The parameter is only visible in
"Heating" or "Heating and cooling"
operating modes (if necessary with
additional levels).
Lower the setpoint
temperature during
Night mode (heating)
(-128...0) * 0.1 K
-128...
-40
...0
The value by which the night setpoint
temperature for heating is lowered
compared to the heating comfort
temperature.
The parameter is only visible in
"Heating" or "Heating and cooling"
operating modes (if necessary with
additional levels).
Raise the setpoint
temperature during
standby operating mode
(cooling)
(-128...127) * 0.1 K
0...
20
...127
The value by which the standby setpoint
temperature for cooling is lowered
compared to the cooling comfort
temperature.
The parameter is only visible in
"Cooling" or "Heating and cooling"
operating modes (if necessary with
additional levels).
Raise the setpoint
temperature during
Night mode (cooling)
(-128...127) * 0.1 K
0...
40
...127
The value by which the night
temperature for cooling is lowered
compared to the cooling comfort
temperature.
Page 300 of 347
Software "Smart Control 501511"
Parameters