Art. No. SC 1000 KNX
T
Comfort setpoint add. level Heating
≤ T
Comfort setpoint basic level Heating
≤ T
Comfort setpoint basic level Cooling
≤ T
Comfort
setpoint add. level Cooling
T
Standby setpoint add. level Heating
≤ T
Standby setpoint basic level Heating
≤ T
Standby setpoint basic level Cooling
≤ T
Standby
setpoint add. level Cooling
T
Standby setpoint heating
≤ T
Comfort setpoint heating
≤ T
Comfort setpoint cooling
≤ T
Standby setpoint cooling
or
T
Comfort setpoint add. level Heating
≤ T
Comfort setpoint basic level Heating
≤ T
Comfort setpoint basic level Cooling
≤ T
Comfort
setpoint add. level Cooling
T
Night setpoint add. level Heating
≤ T
Night setpoint basic level Heating
≤ T
Night setpoint basic level Cooling
≤ T
Night setpoint add. level
Cooling
T
Night setpoint heating
≤ T
Comfort setpoint heating
≤ T
Comfort setpoint cooling
≤ T
Night setpoint cooling
deadband and deadband positions in the combined heating and cooling operating mode
The comfort setpoint temperatures for heating and cooling are derived from the basic setpoint in
consideration of the adjusted deadband. The deadband (temperature zone for which there is
neither heating nor cooling) is the difference between the comfort setpoint temperatures.
The "deadband between heating and cooling", "deadband position" parameters as well as the
"Basic temperature after reset" parameter are preset in the ETS configuration. One
distinguishes between the following settings...
-
deadband = "symmetrical"
The deadband preset in the ETS is divided into two parts at the basic setpoint. The comfort
set-temperatures are derived directly from the basic setpoint resulting from the half Dead
band.
The following applies...
T
Basic setpoint
– ½T
deadband
= T
Comfort heating setpoint
and
T
Basic setpoint
+ ½T
deadband
= T
Comfort setpoint cooling
-> T
Comfort cooling setpoint
– T
Comfort heating setpoint
= T
deadband
-> T
Comfort cooling setpoint
≥ T
Comfort heating setpoint
-
deadband position = "Asymmetrical"
With this setting the comfort setpoint temperature for heating equals the basic setpoint. The
deadband preset in the ETS is effective only from the basic setpoint in the direction of
comfort temperature for cooling. Thus the comfort set-temperature for cooling is derived
directly from the comfort setpoint for heating.
The following applies...
T
Basic setpoint
= T
Comfort heating setpoint
-> T
Basic setpoint
+ T
deadband
= T
Comfort heating setpoint
-> T
Comfort cooling setpoint
– T
Comfort heating setpoint
= T
deadband
-> T
Comfort cooling setpoint
≥ T
Comfort heating setpoint
Setpoint presettings in the ETS
Temperature setpoints can be preset for each operating mode in the ETS as part of first
configuration. It is possible to configure the setpoints for the "Comfort", "Standby" and "Night"
modes in the ETS plug-in. The setpoint temperatures can later be adapted during regular
operation by KNX communication objects if desired.
The "Frost/heat protection" operating mode allows the separate configuration of two
temperature setpoints for heating (frost protection) and cooling (heat protection) solely in the
Page 196 of 347
Software "Smart Control 501511"
Functional description