![Jung Smart Control SC 1000 KNX Скачать руководство пользователя страница 33](http://html1.mh-extra.com/html/jung/smart-control-sc-1000-knx/smart-control-sc-1000-knx_product-documentation_2031686033.webp)
Art. No. SC 1000 KNX
4.2.3.3 Room temperature controller
Objects for room temperature measurement
Function:
Room temperature measurement
Object
h
64
Function
Actual-temperature
Name
C.Output
Type
2 byte
DPT
9.001
Flag
C, -, T, R
Description
2-byte object for the display of the actual temperature (room temperature),
which is determined by the controller. Possible value range:
-99.9 °C to +99.9 °C / Measurement range of internal temperature sensor:
0 °C to +40 °C.
The temperature value is always output in the format "°C".
Function:
Room temperature measurement
Object
h
65
Function
Received temperature
Name
C.Input
Type
2 byte
DPT
9.001
Flag
C, W, -, (R)
1
Description
2-byte object for coupling an external KNX/EIB room temperature sensor.
Thus cascading of multiple temperature sensors for room temperature
measurement. Possible range of values: -99.9 °C to +99.9 °C.
The temperature value must always be specified in the format "°C".
Object for setpoint temperature specification
Function:
Setpoint temperature specification
Object
h
80
Function
Basic setpoint
Name
C.Input
Type
2 byte
DPT
9.001
Flag
C, W, -, (R)
1
Description
2-byte object for external setting of basic setpoint. Depending on the operating
mode, the possible range of values is limited by the configured frost protection
and/or heat protection temperature.
The temperature value must always be specified in the format "°C".
1: For reading, the R-flag must be set. The last value written to the object via the bus will be
read.
2: For reading, the R-flag must be set. The last value written to the object via the bus or by the
device will be read.
Page 33 of 347
Software "Smart Control 501511"
Object table