Art. No. SC 1000 KNX
"Operation concept = long – short"!
Full-surface operation
enabled
disabled
When the full-surface operation is
enabled, the ETS shows the following
parameters. Full-surface operation can
only be programmed if "Operation
concept = long – short or short"!
Function for full-surface
operation
Switching
Scene recall without
storage function
Scene recall with storage
function
In case of full-surface operation, this
parameter defines the function that is to
be used. The ETS shows the
corresponding communication object
and the other parameters.
If the push button sensor is to recall a
scene with storage function by full-
surface actuation, it will make a
distinction between a brief press (less
than 1 s), a sustained press (longer than
5 s) and an invalid button-press
(between 1 s and 5 s). A brief press
recalls the scene, a sustained press
stores a scene and an invalid full-
surface operation is ignored.
Visible only if "Full-surface operation =
enabled"!
Command for full-
surface operation
ON
OFF
TOGGLE
This parameter defines the value of the
transmitted telegram when a full-surface
operation has been sensed. "TOGGLE"
changes over the current object value.
Visible only if "Full-surface operation =
enabled"!
Scene number (1...64)
1
, 2, ... 64
This parameter defines the scene
number which is to be transmitted to the
bus after a scene recall or during
storage of a scene.
Visible only if "Full-surface operation =
enabled"!
The following parameters are only visible for the rocker function "Value transmitter 1 byte"...
Function
Rocker X.1 /
X.2 no function
Rocker X.1: 0...255 /
Rocker X.2: 0...255 /
Rocker X.1: 0...100 % /
Rocker X.2: 0...100 %
Rocker X.1: 0...255 /
Rocker X.2: no function
Rocker X.1: 0...100 % /
A rocker configured as "Value
transmitter 1 byte" permits selecting
whether the values to be transmitted are
interpreted as integers from 0 to 255 or
as a percentage from 0 % to 100 %. The
following parameters and their settings
depend on this distinction.
Page 316 of 347
Software "Smart Control 501511"
Parameters