Art. No. SC 1000 KNX
Yes
No
On "Yes" the push button sensor
transmits a telegram for stopping the
dimming process when the rocker is
released. When the push button sensor
transmits telegrams for dimming in
smaller levels, the stop telegram is
generally not needed.
Telegram
repeat?
Yes
No
This parameter can be used to activate
telegram repetition for dimming. With the
button held down, the push button
sensor will then transmit the relative
dimming telegrams (in the programmed
level width) until the button is released.
Time between two
telegrams
200 ms
300 ms
400 ms
500 ms
750 ms
1 sec
2 sec
This parameter defines the interval at
which the dimming telegrams are
automatically repeated in the telegram
repetition mode. Visible only if
"Telegram repetition = Yes"!
Full-surface operation
enabled
disabled
When the full-surface operation is
enabled, the ETS shows the following
parameters.
Function for full-surface
operation
Switching
Scene recall without
storage function
Scene recall with storage
function
In case of full-surface operation, this
parameter defines the function that is to
be used. The ETS shows the
corresponding communication object
and the other parameters.
If the push button sensor is to recall a
scene with storage function by full-
surface actuation, it will make a
distinction between a brief press (less
than 1 s), a sustained press (longer than
5 s) and an invalid button-press
(between 1 s and 5 s). A brief press
recalls the scene, a sustained press
stores a scene and an invalid full-
surface operation is ignored.
Visible only if "Full-surface operation =
enabled"!
Command for full-
surface operation
ON
OFF
TOGGLE
This parameter defines the value of the
transmitted telegram when a full-surface
operation has been sensed. "TOGGLE"
changes over the current object value.
Visible only if "Full-surface operation =
enabled"!
Scene number (1 … 64)
1
, 2, ... 64
This parameter defines the scene
number which is to be transmitted to the
Page 314 of 347
Software "Smart Control 501511"
Parameters