Art. No. SC 1000 KNX
-
"Transmit individual state"
The 1 bit status object "Controller status, ..." contains the status information selected by the
"Single status" parameter. Meaning of the status signals:
"Comfort mode active" -> Active if operating mode "Comfort" or a comfort extension is
activated.
"Standby mode active" -> active if the "standby " operating mode is activated.
"Night-mode active" -> active if the "night " operating mode is activated.
"Frost/heat protection active" -> active if the "frost/heat protection" operating mode is
activated.
"Controller disabled" -> Active if controller disable is activated (dew point mode).
"Heating / cooling" -> Active if heating is activated and inactive if cooling is activated.
Inactive if controller is disabled.
"Controller inactive" -> Active with the "heating and cooling" operating mode when the
measured room temperature lies within the dead zone. This status information is always "0"
for the individual "Heating" or "Cooling" operating modes. Inactive if controller is disabled.
"Frost alarm" -> Is active if the detected room temperature reaches or falls below +5 °C.
This status signal will have no special influence on the control behaviour.
i
Upon a reset, the status objects will be updated after the initialisation phase. After this,
updating is performed cyclically every 30 seconds in parallel with the command value
calculation of the controller command values. Telegrams are only transmitted to the bus
when the status changes.
Page 211 of 347
Software "Smart Control 501511"
Functional description