Art. No. SC 1000 KNX
Object for additional command value output, PWM additional heating and combined
valve PWM additional heating/cooling
Function:
Command value
Object
h
101
Function
PWM cmd. value, add.
heating
Name
C.Output
Type
1 byte
DPT
5.001
Flag
C, -, T, (R)
1
Description
1-byte object to output the internal continuous command value of a PWM
controller for additional heating in two-level operation. This object is only
available in this way if the type of feedback control is configured to
"Continuous PI control". In addition to the switching 1 bit command value of
the PWM, the calculated continuous command value of the controller can also
be transmitted to the bus and displayed, e.g. in a visualisation.
Function:
Command value
Object
h
101
Function
PWM comm. value, add.
level
Name
C.Output
Type
1 byte
DPT
5.001
Flag
C, -, T, (R)
1
Description
1-byte object to output the combined continuous command value of a PWM
feedback controller for additional level in two-level operation. This object is
only available in this way if the command values for heating and cooling mode
are output to a shared object (parameter-dependent). The type of feedback
control must also be configured to "Switching PI control (PWM)". In addition to
the switching 1 bit command value of the PWM, the calculated continuous
command value of the controller can also be transmitted to the bus and
displayed, e.g. in a visualisation.
Object for additional command value output, PWM cooling
Function:
Command value
Object
h
102
Function
PWM command value for
cooling / PWM command
value, basic cooling
Name
C.Output
Type
1 byte
DPT
5.001
Flag
C, -, T, (R)
1
Description
1-byte object to output the internal continuous command value of a PWM
feedback controller of the cooling mode. In two-level cooling mode, command
value output for the basic cooling. This object is only available in this way if the
type of feedback control is configured to "Switching PI control (PWM)". In
addition to the switching 1 bit command value of the PWM, the calculated
continuous command value of the controller can also be transmitted to the bus
and displayed, e.g. in a visualisation.
1: For reading, the R-flag must be set. The last value written to the object via the bus or by the
device will be read.
Page 43 of 347
Software "Smart Control 501511"
Object table