Art. No. SC 1000 KNX
either be activated or deactivated using
the 1-bit communication object
"Command value limit", or be
permanently active.
Command value limit
after reset
Deactivated
Activated
When controlling via the object, it is
possible to have the controller activate
the command value limit automatically
after bus voltage return or an ETS
programming operation. This parameter
defines the initialisation behaviour here.
In the "Deactivated" setting, the
command value limit is not automatically
activated after a device reset. A "1"
telegram must first be received via the
"Command value limit" object for the
limit to be activated.
In the "Activated" setting, the controller
activates the command value limit
automatically after a device reset. To
deactivate the limit a "0" telegram must
be received via the "Command value
limit" object. The limit can be switched
on or off at any time using the object.
This parameter is only visible with
"Command value limit = can be
activated via object"!
Minimum command
value for heating
(optionally also for basic
and additional level)
5%
, 10%, 15%, 20%, 25%,
30%, 35%, 40%, 45%, 50%
The "Minimum command value"
parameter specifies the lower command
value limiting value for heating. With an
active command value limit, the set
minimum command value is not
undershot by command values. If the
controller calculates smaller command
values, it sets the configured minimum
command value. The controller
transmits a 0 % command value if no
more heating or cooling energy has to
be demanded.
Maximum command
value for heating
(optionally also for basic
and additional level)
55%, 60%, 65%, 70%,
75%, 80%, 85%, 90%,
95%
, 100%
The "Maximum command value"
parameter specifies the upper command
value limiting value for heating. With an
active command value limit, the set
maximum command value is not
exceeded. If the controller calculates
larger command values, it sets the
configured maximum command value.
Minimum command
value for cooling
(optionally also for basic
and additional level)
5%
, 10%, 15%, 20%, 25%,
30%, 35%, 40%, 45%, 50%
The "Minimum command value"
parameter specifies the lower command
value limiting value for cooling. With an
active command value limit, the set
minimum command value is not
undershot by command values. If the
controller calculates smaller command
values, it sets the configured minimum
Page 294 of 347
Software "Smart Control 501511"
Parameters