![Jung Smart Control SC 1000 KNX Скачать руководство пользователя страница 21](http://html1.mh-extra.com/html/jung/smart-control-sc-1000-knx/smart-control-sc-1000-knx_product-documentation_2031686021.webp)
Art. No. SC 1000 KNX
4.2 Software "Smart Control 501511"
4.2.1 Scope of functions
Functions of the display and touch sensor surface
-
The Smart Control is a control and display unit for controlling and visualising building
functions. The device has a TFT graphic colour screen (10.9 cm, 800 x 480 pixels, 16.7
million colours) with a touchscreen sensor surface.
-
Up to 30 KNX controllable channels (switching, dimming, blind, ...) can be subdivided in up
to 8 different rooms. In addition, the channels are also allocated to function units (light,
shading, heating, ...). Up to 8 function units are available for assignment.
-
The device has a user interface that is clearly and logically structured according to
functions, rooms and favourites. The individual rooms are recalled via a room page in
which the functions of each room can be controlled centrally and efficiently. Function units
can be recalled via a function page in which room-independent and function-oriented
control of the building functions is possible. In addition, it is possible to recall frequently
used KNX functions via start and favourite pages.
-
The KNX channels can be configured to the functions "switching", "dimming (Start/Stop)",
"dimming (brightness value)", "Venetian blind' (Step/Move/Step)", "Venetian blind
(position)", "scene extension", "1-byte value transmitter" and "2-byte value transmitter". In
addition, the functions "Operating mode switchover, internal", "Setpoint shift, internal" and
"Fan controller, internal" are used to operate the integrated room temperature controller.
The "ASCII Text" channel function is purely a display function and is used to display
running texts, whose contents are determined by data from the KNX bus.
-
Two operation concepts for elements on the touch surface: Selection operation (separate
display and operating areas / operation requires the selection of an element that can then
be operated) and direct operation (shared display and operating area / touching of the
sensor surface causes the immediate execution of the function).
-
Operating elements on the touch surface can - depending on the function - be evaluated as
a rocker switch (double-surface principle) or as a button (single surface principle).
-
KNX channels have - depending on the function - up to three status elements: Status text
or value, status icon and bar graph displays. Consequently, a visualization of the KNX
system can also take place in addition to the control.
-
Display of room temperature and date at a central point in the display.
-
Measured values of a KNX weather station can optionally be displayed on a separate
display page. Displayable values are the wind speed, twilight threshold, external brightness
and temperature, precipitation, angle of the sun and up to any 4 different additional external
2-byte values that can be formatted for display. The measured values are displayed by
symbols and text in a form adapted to the display concept.
-
Controllable display lighting. Switching on by means of an operation or communication
object. Switching off is possible via the object or time-controlled.
Functions of the push-button extension module (optional)
-
Each operating area can either be used as a single rocker or as two independent buttons.
-
For push button function either double-surface or single-surface principle.
-
Each rocker can be used for the functions 'switching', 'dimming', 'Venetian blind', '1 byte
value transmitter', '2-byte value transmitter', 'scene extension' and '2-channel operation'.
-
Each button can be used for the functions "switching", "dimming", "Venetian blind", "1 byte
value transmitter", "2-byte value transmitter", "scene extension" and "2-channel operation",
"operating mode switchover, internal" and "setpoint shift, internal".
-
Each operating area has two status LEDs. When a status LED is internally connected with
the rocker or the button, it can signal a button-press or the current status of a
communication object. The status indication can also be in inverted form. When a status
LED is not dependent on the rocker or button, it can be permanently on or off, indicate the
status of an independent communication object, the operating state of a room temperature
controller or the result of a comparison between signed or unsigned 1 byte values.
-
The rockers or buttons can be disabled via a 1-bit object.
-
All LEDs of the push-button extension module can flash simultaneously in the event of an
alarm message.
Page 21 of 347
Software "Smart Control 501511"
Scope of functions