Art. No. SC 1000 KNX
Output of the heating
basic level command
value
Inverted (under current, this
means closed)
Normal (under current,
this means opened)
At this point, it is possible to specify
whether the command value telegram
for the heating basic level is output
normally or in inverted form.
This parameter is only visible if the
operating mode "Heating" or "Heating
and cooling" is configured along with
two-level operation.
Output of the heating
additional level
command value
Inverted (under current, this
means closed)
Normal (under current,
this means opened)
At this point, it is possible to specify
whether the command value telegram
for the heating additional level is output
normally or in inverted form.
This parameter is only visible if the
operating mode "Heating" or "Heating
and cooling" is configured along with
two-level operation.
Output of the cooling
command value
Inverted (under current, this
means closed)
Normal (under current,
this means opened)
At this point, it is possible to specify
whether the command value telegram
for cooling is output normally or in
inverted form.
This parameter is only visible if the
operating mode "Cooling" or "Heating
and cooling" is configured and not two-
level operation.
Output of the cooling
basic level command
value
Inverted (under current, this
means closed)
Normal (under current,
this means opened)
At this point, it is possible to specify
whether the command value telegram
for the cooling basic level is output
normally or in inverted form.
This parameter is only visible if the
operating mode "Cooling" or "Heating
and cooling" is configured along with
two-level operation.
Output of the cooling
additional level
command value
Inverted (under current, this
means closed)
Normal (under current,
this means opened)
At this point, it is possible to specify
whether the command value telegram
for the cooling additional level is output
normally or in inverted form.
This parameter is only visible if the
operating mode "Cooling" or "Heating
and cooling" is configured along with
two-level operation.
Command value limit
Deactivated
continuously activated
can be activated via object
The command value limit allows the
restriction of calculated command
values to the range limits "minimum"
and "maximum". The limits are
permanently set in the ETS and, if
command value limitation is active, can
be neither undershot or exceeded during
device operation.
The "Command value limit" parameter
defines the mode of action of the limiting
function. The command value limit can
Page 293 of 347
Software "Smart Control 501511"
Parameters