Art. No. SC 1000 KNX
weekday of the switching time is
assigned.
Saturday
not active
active
This parameter specifies whether the
switching time event is to take place on
Saturdays. In the "active" setting, the
weekday of the switching time is
assigned.
Sunday
not active
active
This parameter specifies whether the
switching time event is to take place on
Sundays. In the "active" setting, the
weekday of the switching time is
assigned.
Astro
No
Light
Blind
This parameter defines whether the
astro function is activated for the
switching time event concerned. The
parameter additionally defines the astro
behaviour which determines whether a
lighting (setting "light") or a blind, shutter
or awning (setting "shading") is activated
by the astro function. In the "No" setting,
the astro function is inactive for the
switching time.
Random offset
Yes
No
This parameter specifies whether the
random function is activated for the
switching time event concerned. If the
setting is "yes", the assigned switching
time is triggered offset in a set random
period (+/- 15 minutes). The "no" setting
deactivates the random function.
Channel no.
Not assigned
Channel 1 : Designation,
channel 1
..
Channel 30 : Designation,
channel 30
For each switching time it is necessary
to specify which KNX channel it affects.
The parameter "Channel no." assigns
the switching time to one of the KNX
channels (1...30) available in the device.
Care must be taken to ensure that only
channels are allocated that are also
available in the channel configuration in
the parameter nodes "channels..." i.e.
were configured with channel functions!
Channels 24...30 are only available and
consequently only assignable to a
switching time if no weather station page
is configured.
Switching value
ON/Lowering
OFF/Raising
Depending on the function of the
allocated KNX channel, the switching
time executes a channel command
when executing a switching time. This
parameter defines which channel
Page 306 of 347