![Jung Smart Control SC 1000 KNX Скачать руководство пользователя страница 266](http://html1.mh-extra.com/html/jung/smart-control-sc-1000-knx/smart-control-sc-1000-knx_product-documentation_2031686266.webp)
Art. No. SC 1000 KNX
Displaying status value
Yes
No
A status value can be displayed
optionally below the text name, which
displays values in plain text ("0...255" /
"0...100 %") depending on the object
value of the value feedback of an
actuator. The data format of this status
value indicator is determined by the ETS
"Function" parameter. In the function as
"value transmitter 0%...100%", the
displayed value is supplemented
automatically by the unit "%".
After a device reset, the display shows
"---" "---%" until a feedback object value
of the status text is received.
Function
Value transmitter 0...255
Value transmitter 0…100 %
With the channel function "1-byte value
transmitter" telegrams in compliance
with the KNX data types 5.010
(unformatted / 0...255) and 5.001
(Scaling / 0...100%) can be transmitted
to the bus. A sensor operation triggers
the value telegram configured in the
ETS. The ETS "Function" parameter
determines the data format of the object
and specifies which value range the
channel function uses. The channel can
optionally process integers from 0…255
or values within a range of 0…100%.
The scaling of the status indications also
adapts itself depending on this setting.
Surface evaluation
Button function (single
surface)
Display function
In the function "1-byte value transmitter",
the sensor element is always executed
as a push-button function and does not
distinguish between any short and long
operations. As an alternative to the
operating function, it is possible to
deactivate the sensor surface in the
ETS. To do this, set this parameter to
"Display function". In this case, the
channel concerned only works as a
display function for value visualization.
Consequently, touching the sensor or
display elements does not induce any
response.
Value on pressing the
button
0
...255
This parameter defines the value
transmitted to the bus on pressing the
sensor surface via the object "1-byte
value transmitter".
This parameter is only visible when the
"surface evaluation" is configured to
"Button function (single surface)".