Art. No. SC 1000 KNX
Split unit (4 K / 90 min)
via control parameter
setting, it is possible to set the control
parameters in a manner deviating from
the predefined values within specific
limits.
This parameter is only visible if "Type of
cooling control = PI control".
Proportional range
cooling
(10...127) * 0.1 K
10...
50
...127
Separate setting of the "Proportional
range" control parameter.
This parameter is only visible if "Type of
cooling = via control parameter" and the
cooling control type "PI control".
Reset time cooling
(0...255) * 1 min; 0 =
inactive
0...
150
...255
Separate setting of the "Reset time"
control parameter.
This parameter is only visible if "Type of
cooling = via control parameter" and the
cooling control type "PI control".
Top hysteresis of the
2-point controller
cooling
(5...127) * 0.1 K
5
...127
Definition of top hysteresis (switch-on
temperatures) of the cooling.
This parameter is only visible if "Type of
cooling control = Switching 2-point
feedback control (ON/OFF)".
Cooling
2-point controller
hysteresis lower limit
(-128...–5) * 0.1 K
-128...
-5
Definition of bottom hysteresis (switch-
off temperatures) of the cooling.
This parameter is only visible if "Type of
cooling control = Switching 2-point
feedback control (ON/OFF)".
Operating mode switch-
over
Via value (1 byte)
Via switching (4 x 1 bit)
In the setting "Via value (1-byte) the
change-over of the operating modes via
the bus takes place according to the
KNX specification via a 1-byte value
object. In addition, a higher-ranking
forced-object is available for this setting.
In the setting "Via switching (4 x 1 bit)
" the ‘classic’ change-over of the
operating modes via the bus is via four
separate 1-bit objects.
Operation mode after
reset
Restore operation mode
before reset
Comfort mode
Standby mode
Night operation
Frost/heat protection mode
This parameter specifies which
operating mode is set immediately after
a device reset.
With "Restore operation mode before
reset": The mode set before a reset
according to the operating mode object
or by push button function (normal
priority) will be restored after the
initializing phase of the device.
Operating modes set by a function with
a higher priority before the reset
(Forced, Window status, Presence
Page 287 of 347
Software "Smart Control 501511"
Parameters