Art. No. SC 1000 KNX
command should be executed for the
channel functions "switching", "dimming
(Start/Stop)" and "Venetian blind/shutter
(Step/Move/Step)".
The ETS parameters "switching value",
"1-byte switching value" and "2-byte
switching value" are always visible. The
function of the allocated KNX channel
defines which of these parameters is
enabled In the channel functions "scene
extension" and "operating mode
switchover internal" none of the
aforementioned parameters are
enabled. In these cases, the channel
command of the timer is specified
directly by the configuration of the KNX
channel.
1-byte switching value
0...
255
Depending on the function of the
allocated KNX channel, the switching
time executes a channel command
when executing a switching time. This
parameter defines which channel
command should be executed for the
channel functions "dimming (brightness
value)", "Venetian blind/shutter
(position)" and "1-byte value
transmitter".
The ETS parameters "switching value",
"1-byte switching value" and "2-byte
switching value" are always visible. The
function of the allocated KNX channel
defines which of these parameters is
enabled In the channel functions "scene
extension" and "operating mode
switchover internal" none of the
aforementioned parameters are
enabled. In these cases, the channel
command of the timer is specified
directly by the configuration of the KNX
channel.
2-byte switching value
-671088.64...
0.0
...670760.96
Depending on the function of the
allocated KNX channel, the switching
time executes a channel command
when executing a switching time. This
parameter defines which channel
command should be executed for the
channel functions "2-byte value
transmitter" and "setpoint shift, internal".
The value that the user enters in the
entry field is converted by the ETS
PlugIn to the KNX data type 9.0xx
(floating-point numbers) and written in
the ETS database. This can result in
value adjustments due to rounding.
In the channel function "setpoint shift
internal", it should be noted that the
device only accepts values within the
value range of the setpoint shift
(-4...0...+4). Entered values which
Page 307 of 347
Software "Smart Control 501511"
Parameters