![Jung Smart Control SC 1000 KNX Скачать руководство пользователя страница 265](http://html1.mh-extra.com/html/jung/smart-control-sc-1000-knx/smart-control-sc-1000-knx_product-documentation_2031686265.webp)
Art. No. SC 1000 KNX
Function
Scene extension without
storage function
Scene extension with
storage function
Recall internal scene
without storage function
Recall internal scene with
storage function
This parameter specifies how the scene
extension works. In the scene extension
function, the device with a sensor
surface operation transmits a preset
scene number to the bus via a separate
communication object. This feature
permits recalling scenes stored in other
devices and also storing them, if the
storage function is used. The recall of an
internal scene does not result in a
telegram being transmitted to the bus.
This function can be used to recall or –
with the storage function – to store the
up to 8 scenes stored internally in the
local device as well.
The channel function "scene extension"
distinguishes between short and long
operations of the sensor surface. In the
setting "... without storage function", an
operation triggers the simple recall of a
scene. In the setting "... with storage
function", the device monitors the length
of the actuation. A sensor surface
operation of less than five seconds
results in a simple recall of the scene as
described above. After an operation of
more than five seconds, the device
generates a storage instruction.
Scene number on
pressing the button
1
...64
This parameter defines the scene
number for a scene recall or scene
storage function. This number is
transmitted to the bus via the scene
extension object.
This parameter is only visible for the
function as scene extension.
Scene number on
pressing the button
1
...8
This parameter defines the scene
number for an internal scene recall or
internal scene storage function.
This parameter is only visible in the
function for recalling or saving internal
scenes.
The following parameters are only visible for the function "Value transmitter 1 byte"...
Icons
no icon
Icon 1: Venetian blind
Icon 2: Vertical slat
Icon 3: Shutter
Icon 4: Roof window
Icon 5: Awning
Icon 6: Brightness value/
dimming value
An icon can be displayed in the lower
area of the channel display element.
This parameter defines which type of
status icon is used in the display
element. The character of the status
icon changes depending on the
feedback value thereby enabling the
value status (e.g. brightness value or
blind/shutter position) of the activated
KNX channel to be read clearly.
The icon can be omitted optionally in the
display (setting: no icon).
Page 265 of 347
Software "Smart Control 501511"
Parameters