![Jung Smart Control SC 1000 KNX Скачать руководство пользователя страница 328](http://html1.mh-extra.com/html/jung/smart-control-sc-1000-knx/smart-control-sc-1000-knx_product-documentation_2031686328.webp)
Art. No. SC 1000 KNX
if "Function = 0...100 %"!
Value adjustment by
long button-press
enabled
disabled
If value adjustment by long button-press
is enabled, the ETS shows further
parameters.
Value adjustment begins, when the
button is held down for more than 5 s. In
this case, the respective status LED
flashes as a sign that a new telegram
has been transmitted.
Starting value in case of
value adjustment
Same as configured value
Same as value after last
adjustment
Same as value from
communication object
Value adjustment can begin with
different starting values. In the setting
"Same as parameterised value", after
each long press the pushbutton sensor
always starts with the value
programmed in the ETS.
In the setting "Same as value after last
adjustment", after a long press the
pushbutton sensor starts with the value
transmitted by itself or by another device
with this group address as the last
value.
In the setting "Same as value from
communication object", after a long
press the pushbutton sensor starts with
the value transmitted by itself or by
another device with this group address
as the last value.
This parameter is only visible if "Value
adjustment by long button-press =
enabled"!
Direction of value
adjustment
Upwards
Downwards
Toggling (alternating)
With a long press, the push button
sensor can either vary the values always
in the same direction or it stores the
direction of the last adjustment and
reverses it on the next button-press.
Visible only if "Value adjustment by long
button-press = enabled"!
Step width (1...15)
1
...15
In a value adjustment, the pushbutton
sensor determines the new telegram
value from the previous value and the
preset step width. If the value falls below
the lower limit of the adjustment range
(0 or 0 %) or if it exceeds the upper limit
(255 or 100%), the sensor adapts the
step width of the last step automatically.
Visible only if "Value adjustment by long
button-press = enabled"!
Time between two
telegrams
0.5 sec
1 sec
2 sec
3 sec
In a value adjustment, the pushbutton
sensor determines the new telegram
value from the previous value and the
preset step width. If the value falls below
Page 328 of 347
Software "Smart Control 501511"
Parameters