Art. No. SC 1000 KNX
The parameter is only visible in
"Cooling" or "Heating and cooling"
operating modes (if necessary with
additional levels).
Change-over between
heating and cooling
Automatic
Via object (heating/cooling
change-over)
In a configured mixed mode it is
possible to switch over between heating
and cooling.
With "Automatic": Depending on the
operating mode and the room
temperature, the change-over takes
place automatically.
With "Via object (heating/cooling
change-over)": The change-over takes
place only via the object "Heating /
cooling change-over".
Heating / cooling
operating mode after
reset
Heating
Cooling
Operating mode before
reset
The preset operating mode for after the
return of the bus voltage is specified
here.
Only visible if "Change-over between
heating and cooling = via object"!
Automatic heating/
cooling switch-over
transmission
On changing the
operating mode
On changing the output
value
Here, it is possible to specify when a
telegram is transmitted automatically
onto the bus via the object "Heating /
cooling change-over".
Only visible if "Change-over between
heating and cooling = automatic".
Cyclical transmission
heating/cooling change-
over
(0...255) * 1 min;
0 = inactive
0
...255
This parameter specifies whether the
current object status of the "Heating /
cooling change-over" object should be
output cyclically to the bus on an
automatic change-over. The cycle time
can be set here. The "0" setting will
deactivate the periodic transmission of
the object value.
Only visible if "Change-over between
heating and cooling = automatic".
Setpoint temperature
limit in cooling operation
No limit
Only difference to outdoor
temperature
Only max. setpoint
temperature
Max. setpoint and
difference to outdoor
temperature
Optionally, the setpoint temperature limit
can be enabled here, which is only
effective in cooling operation. If
necessary, the controller limits the
setpoint temperature to specific values
and prevents an adjustment beyond the
limits.
"Only difference to outdoor temperature"
setting, the outdoor temperature is
monitored and compared to the active
setpoint temperature in this setting. The
specification of the maximum
temperature difference to the outdoor