![Jung Smart Control SC 1000 KNX Скачать руководство пользователя страница 27](http://html1.mh-extra.com/html/jung/smart-control-sc-1000-knx/smart-control-sc-1000-knx_product-documentation_2031686027.webp)
Art. No. SC 1000 KNX
Function:
2-byte value transmitter
Object
h
0
Function
Temperature value
Name
B.Module rocker/
B.Module button 1
1,2
Type
2 byte
DPT
9.001
Flag
C, W, T,
(R)
3
Description
2 -byte object for the transmission of a temperature value from 0 °C to 40 °C.
If the adjustment of the value is enabled, the object can transmit telegrams
cyclically after a long press with which the value can be reduced or increased
by 1 K.
Function:
2-byte value transmitter
Object
h
0
Function
Brightness value
Name
B.Module rocker/
B.Module button 1
1,2
Type
2 byte
DPT
9.004
Flag
C, W, T,
(R)
3
Description
2-byte object for the transmission of a brightness level value from 0 to 1500
lux. If the adjustment of the value is enabled, the object can transmit cyclical
telegrams after a long press with which the value can be reduced or increased
by 50 lux.
Function:
Scene extension
Object
h
0
Function
Scene extension
Name
B.Module rocker/
B.Module button 1
1,2
Type
1 byte
DPT
18.001
Flag
C, -, T, (R)
3
Description
1-byte object for recalling or for storing one of 64 scenes max. from a scene
push button sensor.
Function:
2-channel operation
Object
h
0
Function
Channel 1 switching
Name
B.Module rocker/
B.Module button 1
1,2
Type
1-bit
DPT
1.xxx
Flag
C, W, T,
(R)
3
Description
1-bit object for the transmission of switching telegrams, if 2-channel operation
is activated.
1: The number of rockers or buttons depends on the planned device variant.
2: The objects have been described for rocker 1 or button 1 as an example. The objects for the
other rockers/buttons are defined in the same way by shifting the object number and changing
the object name.
3: For reading, the R-flag must be set. The last value written to the object via the bus or by the
device will be read.