![Jung Smart Control SC 1000 KNX Скачать руководство пользователя страница 39](http://html1.mh-extra.com/html/jung/smart-control-sc-1000-knx/smart-control-sc-1000-knx_product-documentation_2031686039.webp)
Art. No. SC 1000 KNX
Function:
Command value
Object
h
96
Function
Command value for heating/
cooling / command value,
basic level
Name
C.Output
Type
1 byte
DPT
5.001
Flag
C, -, T, (R)
1
Description
1-byte object to output the combined continuous command value of the
heating and cooling mode. In two-level heating/cooling mode, command value
output for the basic level This object is only available in this way if the
command values for heating and cooling mode are output to a shared object
(parameter-dependent). The type of feedback control must also be configured
to "Continuous PI control".
Function:
Command value
Object
h
96
Function
Command value for heating/
cooling (PWM) / command
value, basic level (PWM)
Name
C.Output
Type
1-bit
DPT
1.001
Flag
C, -, T, (R)
1
Description
1-bit object to output the combined PWM command value of the heating and
cooling mode. In two-level heating/cooling mode, command value output for
the basic level This object is only available in this way if the command values
for heating and cooling mode are output to a shared object (parameter-
dependent). The type of feedback control must also be configured to
"Switching PI control (PWM)".
Function:
Command value
Object
h
96
Function
Command value for heating/
cooling / command value,
basic level
Name
C.Output
Type
1-bit
DPT
1.001
Flag
C, -, T, (R)
1
Description
1-bit object to output the combined switching command value of the heating
and cooling mode. In two-level heating/cooling mode, command value output
for the basic level This object is only available in this way if the command
values for heating and cooling mode are output to a shared object (parameter-
dependent). The type of feedback control must also be configured to
"Switching 2-point feedback control".
Object for command value output, additional heating and combined valve additional
heating/cooling
Function:
Command value
Object
h
97
Function
Cmd. value, additional
heating
Name
C.Output
Type
1 byte
DPT
5.001
Flag
C, -, T, (R)
1
Description
1-byte object to output the continuous command value for additional heating in
two-level operation. This object is only available in this way if the type of
feedback control is configured to "Continuous PI control".
1: For reading, the R-flag must be set. The last value written to the object via the bus or by the
device will be read.
Page 39 of 347
Software "Smart Control 501511"
Object table