Goodrive3000 series medium voltage VFD Goodrive3000 inverter
-86-
Output frequency f
Time t
t1
t2
t3
t4
t1=P01.06 x ACC time (P00.11)
t2=P01.07 x ACC time (P00.11)
t3=P01.06 x DEC time (P00.12)
t4=P01.07 x DEC time (P00.12)
Function
code
Name
Description
Setting range
Default
P01.08
Stop mode
0: Decelerate to stop
1: Coast to stop
0
–1
0
0: Decelerate to stop: after the stop command becomes valid, the VFD decelerates to decrease output
frequency during the set time. When the frequency decreases to 0Hz, the VFD will stop.
1: Coast to stop: after the stop command becomes valid, the VFD immediately ceases the output. The
load coasts to stop at the mechanical inertia.
Function
code
Name
Description
Setting range
Default
P01.09
Starting frequency
of DC braking
0.00
–P00.03 (Max. frequency)
0.00
–P00.03
0.00Hz
P01.10
Waiting time before
DC braking
0.0
–50.0s
0.0
–50.0
0.0s
P01.11
DC braking current 0.0
–100.0% (Motor rated current)
0.0
–100.0
0.0%
P01.12
DC braking time
0.0
–50.0s
0.0
–50.0
0.0s
Starting frequency of DC braking: start the DC braking when running frequency reaches the starting
frequency during stop.
Waiting time before DC braking: the VFD blocks the output before starting DC braking. Start the DC
braking after the waiting time to prevent overcurrent fault caused by DC braking at high speed.
DC braking current refers to the added DC braking. The higher the current, the greater the braking effect.
DC braking time refers to the retention time of DC braking. If the time is 0, DC braking is invalid and the
VFD will stop at the set deceleration time.
P01.04
Acceleration
P13.14
P01.23
Constant speed
In running
Deceleration
P01.10
P13.15
P01.12
P01.09
Time t