Goodrive3000 series medium voltage VFD MODBUS protocol
-258-
Function
instruction
Address
definition
Data meaning instruction
R/W
characteristics
2005H
The upper limit frequency setting during forward
rotation (0
–Fmax(unit: 0.01Hz))
W
2006H
The upper limit frequency setting during reverse
rotation (0
–Fmax(unit: 0.01Hz))
W
2007H
The upper limit torque of electromotion torque
(0
–3000, 1000 corresponds to the 100.0% of the
rated current of the motor)
W
2008H
The upper limit torque of braking torque
(0
–3000, 1000 corresponds to the 100.0% of the
rated current of the motor)
W
2009H
Special control command word
Bit0
–
1:=00: motor 1 =01: motor 2
=10: motor 3 =11: motor 4
Bit2:=1 torque control prohibit
=0: torque control
W
200AH
Virtual input terminal command , range:
0x000
–0x1FF
W
200BH
Virtual output terminal command , range:
0x00
–0x0F
W
200CH
Voltage setting value (special for V/F separation)
(0
–1000, 1000 corresponds to the 100.0%)
W
200DH
AO output setting 1
(-1000
–1000, 1000 corresponds to 100.0%)
W
200EH
AO output setting 2
(-1000
–1000, 1000 corresponds to 100.0%)
W
SW 1 of the VFD
2100H
0001H:forward running
R
0002H:forward running
0003H:stop
0004H:fault
0005H: POFF state
SW 2 of the VFD
2101H
Bit0: =0: ready for operation
=1: not ready for operation
R
Содержание GD3000-01-055G-12
Страница 1: ......
Страница 27: ...Goodrive3000 series medium voltage VFD HMI 22 4 4 Keypad dimension Figure 4 3 LCD keypad dimension...
Страница 317: ......