Function
code
Name
Description
Setting range
Default Modify
P10.36
PLC restart
0: Restart from the first step
1: Continue to run from the stop
frequency
0
–1
0
◎
P10.37
Multi-step time
unit
0: Second
1: Minute
0
–1
0
◎
P11
group
––Protective parameters
P11.00
Phase loss
protection
0x00
–0x11
LED ones:
0: Disable input phase loss protection
1: Enable input phase loss protection
LED tens:
0: Disable output phase loss protection
1: Enable output phase loss protection
00
–11
11
○
P11.01
Instantaneous
power loss
frequency
decreasing
0: Disabled
1: Enabled
0
–1
0
○
P11.02
Frequency
decreasing
velocity of
instantaneous
power loss
0.00Hz/s
–P00.03Hz/s (Max. frequency) 0.00Hz–P00.03 10.00Hz/s
○
P11.03
Overvoltage
speed loss
protection
0: Disabled
1: Enabled
0
–1
1
○
P11.04
Voltage
protection of
overvoltage stall
120
–150% (standard bus voltage)
120
–150%
130%
○
P11.05
Current limit
action
Ones: current limit
0: Invalid
1: Valid
Tens: overload alarm of hardware
current limit (for factory commissioning)
0: Valid
1: Invalid
00
–11
01
◎