Goodrive3000 series medium voltage VFD Product overview
-7-
Function
Specification
Running
environment
temperature
-10°C
– +50°C
When the temperature exceeds 40°C, derating is required.
Relative humudity
5%
–95%
Storage
temperature
-40°C
– +70°C
Altitude
Less than 1000 meters
When the VFD installation site altitude exceeds 1000 meters, derate
by 1% for every increase of 100 meters.
Ingress protection
rating
Main module: IP00
Cabinet of a standard product: IP20, IP54
2.3 Goodrive3000 four-quadrant VFD technical specifications
2.3.1 Goodrive3000 PWM rectifier technical specifications
Table 2.3 Goodrive3000 PWM rectifier technical specifications
Function
Specification
Power
input
Input voltage (V)
AC 3PH 560V
–760V; rated voltage: 660V
AC 3PH 970V
–1310V; rated voltage: 1140V
AC 3PH 2805V
–3795V; rated voltage: 3300V
Input current (A)
See section 2.4.2 Goodrive3000 four-quadrant VFD.
Input frequency (Hz)
50Hz/60Hz, allowable range: 47
–63Hz
Input efficiency (%)
Above 98%
Input power factor
Above 0.99
Important
protection
function
Overload protection
150% of rated current: 60s, 180% of rated current: 10s
Overvoltage
protection
When the bus voltage is > set overvoltage, overvoltage is reported.
Undervoltage
protection
When the bus voltage is < set undervoltage, undervoltage is
reported.
Input overvoltage
protection
When the input voltage is > set overvoltage, overvoltage is reported.
Input undervoltage
protection
When the input voltage is < set undervoltage, undervoltage is
reported.