Goodrive3000 series medium voltage VFD Goodrive3000 inverter
-108-
Set value
Function
Instruction
operation (Sln)
3-wire control. See specific information in the description of 3-wire
control mode in P05.12.
4
Forward rotation
jogging
As for the frequency and ACC/DEC time at jogging, refer to the
detailed descriptions in P08.06, P08.07 and P08.08.
5
Reverse rotation
jogging
6
Coast to stop
The VFD blocks the output, so the motor is out of control of the VFD
during stopping. The way is usually applied to large load and no
stop time limit. The definition is the same with that in P01.08 and the
function is applicable to remote control.
7
Fault reset
External fault reset function is the same with the function of
STOP/RST on the keypad and it can realize remote fault reset.
8
Operation pause
The VFD slows down to stop but all running parameters are in
memory state, such as PLC parameters, traverse parameters and
PID parameters. When the signals disappear, the VFD will restore
to the state before stopping.
9
External fault input
After the external fault signal is sent to the VFD, the VFD will alarm
the fault and stop.
10
Increasing frequency
setting (UP)
The external terminals modify increasing and decreasing
commands of the VFD when the terminals set the frequency.
COM
K1
K2
UP terminal
DOWN terminal
K3
UP/DOWN
reset terminal
The reset terminals of increasing and decreasing frequency setting
can clear the auxiliary channel frequency set by the internal
UP/DOWN of the VFD so that the frequency reference restores to
the value from the main frequency setting channel.
11
Decreasing
frequency setting
(DOWN)
12
Cancel the
frequency change
setting
13
Shift between A
setting and B setting
The function mainly realizes the shift between frequency setting
channels.
The shift between A and B setting channels can be realized by 13.
The shift between combination setting and A setting channels set by
P00.09 can be realized by 14. The shift between combination
setting and B setting channels set by P00.09 can be realized by 15.
14
Shift between
combination setting
and A setting
15
Shift between
combination setting
and B setting