Goodrive3000 series medium voltage VFD PROFIBUS communication
-291-
Rectifier related function codes
Function
code
Name
Description
Setting range Default
P15.00
Module type
0: Profibus
0
–1
0
P15.01
Profibus/CANopen
module address
0
–127
0
–127
2
P15.02
Received PZD2
0: Invalid
1: Set frequency (0
–Fmax; unit:
0.01Hz)
2: PID reference (range: 0
–1000, 1000
corresponding to 100.0%)
3: PID feedback (range: 0
–1000, 1000
corresponding to 100.0%)
4: Torque setting (-3000
–3000, 1000
corresponding to 100.0% of motor
rated current)
5: Forward rotation upper-limit
frequency setting (0
–Fmax; unit:
0.01Hz)
6: Reverse rotation upper-limit
frequency (0
–Fmax; unit: 0.01Hz)
7: Electromotion torque upper limit
(0
–3000, 1000 corresponding to
100.0% of motor rated current)
8: Braking torque upper limit (0
–2000,
1000 corresponding to 100.0% of motor
rated current)
9: Virtual input terminal command
(range: 0x000
–0x1FF)
10: Virtual output terminal command
(range: 0x00
–0x0F)
11: Voltage setting (special for V/F
separation) (0
–1000, 1000
corresponding to 100.0% of motor
rated voltage)
12: AO setting 1 (-1000
–1000, 1000
corresponding to 100.0%)
13: AO setting 2 (-1000
–1000, 1000
corresponding to 100.0%)
0
–20
0
P15.03
Received PZD3
0
–20
0
P15.04
Received PZD4
0
–20
0
P15.05
Received PZD5
0
–20
0
P15.06
Received PZD6
0
–20
0
P15.07
Received PZD7
0
–20
0
P15.08
Received PZD8
0
–20
0
P15.09
Received PZD9
0
–20
0
P15.10
Received PZD10
0
–20
0
P15.11
Received PZD11
0
–20
0
P15.12
Received PZD12
0
–20
0