Goodrive3000 series medium voltage VFD Goodrive3000 inverter
-137-
Function
code
Name
Description
Setting range
Default
P08.09
Jumping frequency
1
0.00
–P00.03 (Max. frequency)
0.00
–P00.03
0.00Hz
P08.10
Jumping frequency
range 1
0.00
–P00.03 (Max. frequency)
0.00
–P00.03
0.00Hz
P08.11
Jumping frequency
2
0.00
–P00.03 (Max. frequency)
0.00
–P00.03
0.00Hz
P08.12
Jumping frequency
range 2
0.00
–P00.03 (Max. frequency)
0.00
–P00.03
0.00Hz
P08.13
Jumping frequency
3
0.00
–P00.03 (Max. frequency)
0.00
–P00.03
0.00Hz
P08.14
Jumping frequency
range 3
0.00
–P00.03 (Max. frequency)
0.00
–P00.03
0.00Hz
When the set frequency is in the range of the jumping frequency, the VFD will run at the edge of the
jumping frequency.
The VFD can avoid the mechanical resonance point by setting the jumping frequency. The VFD can set
three jumping frequency points. But this function will be invalid if all jumping points are 0.
Set frequency f
Time t
Jumping
frequency2
1/2*jumping range 2
1/2*jumping range 2
Jumping
frequency1
1/2*jumping range 1
1/2*jumping range 1
Jumping
frequency3
1/2*jumping range 3
1/2*jumping range 3
Function
code
Name
Description
Setting range
Default
P08.27
Set running time
0
–65535min
0
–65535
0min
Preset the running time of the VFD. When the accumulative running time achieves the set time, the
multi-function digital output terminal will output the signal of "running time arrival".
Function
code
Name
Description
Setting range
Default
P08.28
Fault reset times
0
–10
0
–10
0
P08.29
Interval time of
0.1
–3600.0s
0.1
–3600.0
1.0s