Goodrive3000 series medium voltage VFD Goodrive3000 inverter
-175-
P19 group
––External temperature detection
Function
code
Name
Description
Setting range
Default
P19.00
Motor temperature
detection
0: Invalid
1: PT100
2: PTC
3: Reserved
4: Reserved
0
–4
0
P19.01
Motor temperature
pre-alarm point
0°C
–200°C
(0°C: pre-alarm invalid)
0°C
–200°C
125°C
P19.02
Motor
overtemperature
fault point
0°C
–200°C
(0°C: pre-alarm invalid)
0°C
–200°C
150°C
P19.03
Motor
overtemperature
action
0: Alarm fault and coast to stop
1: No alarm and keep running
2: No alarm and stop
0
–2
0
P19.04
Starting temperature
of motor temperature
compensation
0
–60.0°C
0
–60.0
40.0°C
P19.05
Motor temperature
compensation
coefficient
0.0
–200.0%
0.0
–200.0
100.0%