9: Reserved
P09.01
Keypad PID
preset
-100.0%
–100.0%
-100.0
–100.0
0.0%
○
P09.02
PID feedback
source
0: AI1 feedback
1: AI2 feedback
2: AI3 feedback
3: HDI pulse feedback
4: MODBUS communication feedback
5: PROFIBUS/CANopen
communication feedback
6: Ethernet communication feedback
7: Reserved
0
–7
0
○
P09.03
PID output
feature
0: PID output is positive.
1: PID output is negative.
0
–1
0
○
P09.04
Proportional gain
(Kp)
0.00
–100.00
0.00
–100.00
1.00
○
P09.05
Integral time(Ti) 0.00
–10.00s
0.00
–10.00
0.10s
○
P09.06
Differential
time(Td)
0.00
–10.00s
0.00
–10.00
0.00s
○
P09.07
Sampling cycle
(T)
0.001
–10.000s
0.001
–10.000
0.100s
○
P09.08
PID control
deviation limit
0.0
–100.0%
0.0
–100.0
0.0%
○
P09.09
Upper limit of PID
output
P09.10
–100.0% (Max. frequency or
voltage)
P09.10
–100.0
100.0%
○
P09.10
Lower limit of PID
output
-100.0%
–P09.09 (Max. frequency or
voltage)
-100.0
–P09.09
0.0%
○
P09.11
Feedback offline
detection value
0.0
–100.0%
0.0
–100.0%
0.0%
○
P09.12
Feedback offline
detection time
0.0
–3600.0s
0.0
–3600.0
1.0s
○
P09.13
PID adjustment
0x0000
–0x1111
LED ones:
0000
–1111
0x0001
○
Содержание GD3000-01-055G-12