Goodrive3000 series medium voltage VFD Goodrive3000 inverter
-111-
Function
code
Name
Description
Setting range
Default
P05.11
ON-OFF filter time 0.000
–1.000s
0.000
–1.000
0.010s
Set the sample filter time of S1
–S8 terminals. If the interference is strong, increase the parameter to
avoid the incorrect operation.
Function
code
Name
Description
Setting range
Default
P05.12
Virtual terminal
setting
0: Virtual terminals are invalid.
1: MODBUS communication virtual
terminals are valid.
2: PROFIBUS/CANopen
communication virtual terminals are
valid.
3: Ethernet communication virtual
terminals are valid.
4: Reserved
0
–4
0
Enable the input function of virtual terminals at communication modes.
Function
code
Name
Description
Setting range
Default
P05.13
Terminal control
running mode
0: 2-wire control 1
1: 2-wire control 2
2: 3-wire control 1
3: 3-wire control 2
0
–3
0
Set the running mode of the terminal control.
0: 2-wire control 1, comply the enable with the direction. This mode is widely used. It determines the
rotation direction of the motor by defined FWD and REV terminal commands.
FWD
REV
COM
K1
K2
Running
command
FWD REV
OFF
OFF
OFF
OFF
ON
ON
ON
ON
Stop
Hold
FWD
running
REV running
1: 2-wire control 2: Separate the enable from the direction. FWD defined by this mode is the enabling one.
The direction depends on the state of the defined REV.