Goodrive3000 series medium voltage VFD Goodrive3000 inverter
-163-
Function
code
Name
Description
Setting range
Default
P14.03
Communication
response delay
0
–200ms
0
–200
5
The function code refers to the interval when the VFD receives data and sends response to the upper
computer. If the response delay is shorter than the processing time, take the processing time as the
standard. If the response delay is longer than the processing time, delay and wait to send data to the
upper computer until the response delay arrival after the system finishes processing data.
Function
code
Name
Description
Setting range
Default
P14.04
Fault time of
communication
timeout
0.1
–60.0s
0.0: Invalid
0.0
–60.0
0.0s
When the function code is set to 0.0, the parameter will be invalid.
When the function code is set to non-zero and the interval between the current and next communication
exceeds the communication timeout, the system will alarm 485 communication fault (CE).
Generally, set the parameter to be invalid. The parameter setting can monitor communication state in
continuous communication system.
Function
code
Name
Description
Setting range
Default
P14.05
Transmission fault
processing
0: Alarm and coast to stop
1: Continue to run without alarm
2: Stop according to stop way without
alarm (only in communication control
mode)
3: Stop according to stop way without
alarm (in all control modes)
0
–3
0
Set the processing ways for transmission fault.
Function
code
Name
Description
Setting range
Default
P14.06
Communication
processing action
LED ones:
0: With response to write operation
1: Without response to write
operation
LED tens:
0: Communication encryption setting
0x00
–0x11
0x00