Goodrive3000 series medium voltage VFD Goodrive3000 inverter
-91-
P02 group
––Motor 1 parameters
Function
code
Name
Description
Setting range
Default
P02.00
Motor 1 type
0: Asynchronous motor
1: Reserved
0
–1
0
Select the type of motor 1.
Function
code
Name
Description
Setting range
Default
P02.01
Asynchronous motor
1 rated power
0.1
–3000.0kW
0.1
–3000.0
Depends
on model
P02.02
Asynchronous motor
1 rated frequency
0.01Hz
–
P00.03 (Max. frequency)
0.01
–P00.03
50.00Hz
P02.03
Asynchronous motor
1 rated speed
1
–
36000rpm
1
–36000
Depends
on model
P02.04
Asynchronous motor
1 rated voltage
0
–
4000V
0
–4000
Depends
on model
P02.05
Asynchronous motor
1 rated current
0.8
–
6000.0A
0.8
–6000.0
Depends
on model
Set the parameters of the asynchronous motor under control.
To ensure control performance, please set values of P02.01
–
P02.05 correctly in accordance with the
parameters on the nameplate of the asynchronous motor.
Goodrive3000 VFDs provide parameter autotuning function from proper parameter setting of the
nameplate.
To ensure control performance, please configure the motor according to the standard motor of the VFD. If
the power is quite different from the standard motor, VFD control performance will decrease obviously.
Note:
Reset the rated power of the motor (P02.01) to initialize the parameters of P02.02
–P02.10.
Function
code
Name
Description
Setting range
Default
P02.06
Asynchronous
motor 1 stator
resistor
0.001
–65.535Ω
0.001
–65.535
Depends
on model
P02.07
Asynchronous
motor 1 rotor
resistor
0.001
–65.535Ω
0.001
–65.535
Depends
on model
Содержание GD3000-01-055G-12
Страница 1: ......
Страница 27: ...Goodrive3000 series medium voltage VFD HMI 22 4 4 Keypad dimension Figure 4 3 LCD keypad dimension...