![INVT GD3000-01-055G-12 Скачать руководство пользователя страница 235](http://html1.mh-extra.com/html/invt/gd3000-01-055g-12/gd3000-01-055g-12_operation-manual_2085697235.webp)
Goodrive3000 series medium voltage VFD Goodrive3000 inverter
-230-
Function
code
Name
Description
Setting range
Default Modify
pre-alarm
P11.13
Output terminal
action during
undervoltage and
auto-reset
0x00
–0x11
LED ones:
0: Action at undervoltage
1: No action at undervoltage
LED tens:
0: Action during auto-reset
1: No action during auto-reset
00
–11
0x00
○
P11.14
Detection value
of speed
deviation
0.0
–50.0%
0.0
–50.0
10.0%
○
P11.15
Detection time of
speed deviation
0.0
–10.0s (No speed deviation
protection at 0.0)
0.0
–10.0
0.5s
○
P11.16
Automatic
frequency-decrea
sing at voltage
drop
0: Invalid
1: Valid
0
–1
0
○
P12
group
––Motor 2 parameters
P12.00
Motor 2 type
0: Asynchronous motor
1: Reserved
0
–1
0
◎
P12.01
Asynchronous
motor 2 rated
power
0.1
–3000.0kW
0.1
–3000.0
Depends
on model
◎
P12.02
Asynchronous
motor 2 rated
frequency
0.01Hz
–P00.03 (Max. frequency)
0.01
–P00.03
50.00Hz
◎
P12.03
Asynchronous
motor 2 rated
speed
1
–36000rpm
1
–36000
Depends
on model
◎
P12.04
Asynchronous
motor 2 rated
voltage
0
–4000V
0
–4000
Depends
on model
◎
P12.05
Asynchronous
motor 2 rated
current
0.8
–6000.0A
0.8
–6000.0
Depends
on model
◎
Содержание GD3000-01-055G-12
Страница 1: ......
Страница 27: ...Goodrive3000 series medium voltage VFD HMI 22 4 4 Keypad dimension Figure 4 3 LCD keypad dimension...