Goodrive3000 series medium voltage VFD Goodrive3000 PWM rectifier
-32-
P05 group
––Input terminals
Function
code
Name
Description
Setting range
Default
P05.01
Polarity selection of
digital input terminals
0x0
–0xF
0x0
–0xF
0x0
Set the polarity of digital input terminals
If set the bit as 0, the input terminal is positive, and when set the bit as 1, the input terminal is negative.
BIT3
BIT2
BIT1
BIT0
S4
S3
S2
S1
Function
code
Name
Description
Setting range
Default
P05.03
Digital input filtering
time
0.000
–1.000s
0.000
–1.000
0.000s
Set the filtering time for S1
–S4 terminal sampling. In the case of strong interference, this parameter
should be increased to avoid malfunction.
Function
code
Name
Description
Setting range
Default
P05.04
S1 terminal function
selection
0: No function
1: Run
2: Fault reset
3: External fault
4: Reserved
5: Run enabling
6: Reserved
7
–
12: Reserved
13: Total electricity consumption
cleared
14: Accumulative power maintain
15: Reserved
0
–15
1
P05.05
S2 terminal function
selection
2
P05.06
S3 terminal function
selection
0
P05.07
S4 terminal function
selection
0
Terminal description:
Setting value
Function
Description
0
No function
PWM rectifier does not act even though there is signal.
Set the unused terminal as non-function to avoid