Goodrive3000 series medium voltage VFD Goodrive3000 inverter
-110-
Set value
Function
Instruction
by P01.12 (DC braking time at stopping).
35
Shift motor 1 to
motor 2
When the terminal is valid, motor 1 will shift into motor 2. When the
terminal is invalid, the running command returns to the original
state.
36
Shift the command to
the keypad
When the terminal is valid, the running command will compel to shift
to keypad running command. When the terminal is invalid, the
running command returns to the original state.
37
Shift the command to
the terminals
When the terminal is valid, the running command will compel to shift
to terminal running command. When the terminal is invalid, the
running command returns to the original state.
38
Shift the command to
the communication
When the terminal is valid, the running command will compel to shift
to communication running command. When the terminal is invalid,
the running command returns to the original state.
39
Pre-exciting
command
Start pre-exciting command of the motor until the terminal becomes
invalid.
40
Consumption power
clear
When the command is valid, the power of the VFD will be cleared.
41
Consumption power
holding
When the command is valid, the current running of the VFD will not
influence the power.
42
External fault input 2 The VFD will alarm and stop after receiving the external fault signal.
43
–
63
Reserved
Function
code
Name
Description
Setting range
Default
P05.10
Polarity of input
terminals
0x000
–0x1FF
0x000
–0x1FF
0x000
The function code is used to set the polarity of the input terminals.
Set the bit to 0, the input terminal is anode.
Set the bit to 1, the input terminal is cathode.
BIT7
BIT6
BIT5
BIT4
BIT3
BIT2
BIT1
BIT0
S8
S7
S6
S5
S4
S3
S2
S1