Goodrive3000 series medium voltage VFD Goodrive3000 inverter
-97-
Function
code
Name
Description
Setting range
Default
source selection
7: PROFIBUS/CANopen
communication setting
8: Ethernet communication setting
9: Reserved
Note:
100% of the setting methods 1
–9 corresponds to the maximum frequency.
Note:
3, 4, 7 and 8 need to use extension cards.
Function
code
Name
Description
Setting range
Default
P03.16
Keypad defined
value of torque
control forward
rotation upper-limit
frequency
0.00Hz
–P00.03
0.00
–P00.03
50.00Hz
P03.17
Keypad defined
value of torque
control reverse
rotation upper-limit
frequency
0.00Hz
–P00.03
0.00
–P00.03
50.00Hz
The function code is used to set upper limit of the frequency, 100% corresponding to the maximum
frequency. P03.16 sets P03.14 and P03.17 sets P03.15.
Function
code
Name
Description
Setting range
Default
P03.18
Electromotion
torque upper-limit
setting source
0: Keypad setting (P03.20 sets
P03.18 and P03.21 sets P03.19)
1: AI1 setting
2: AI2 setting
3: AI3 setting
4: HDI pulse frequency setting
5: MODBUS communication setting
6: PROFIBUS/CANopen
communication setting
7: Ethernet communication setting
8: Reserved
0
–8
0
P03.19
Braking torque
upper-limit setting
source
0
–8
0
The function code is used to select electromotion and braking torque upper-limit setting source.