P11 group
––Protective parameters
Function
code
Name
Description
Setting range
Default
P11.00
Phase loss
protection
0x00
–0x11
LED ones:
0: Disable input phase loss protection
1: Enable input phase loss protection
LED tens:
0: Disable output phase loss
protection
1: Enable output phase loss
protection
00
–11
11
Enable the function of phase loss protection.
Function
code
Name
Description
Setting range
Default
P11.01
Instantaneous
power loss
frequency
decreasing
0: Disabled
1: Enabled
0
–1
0
Enable instantaneous power loss frequency-decreasing function.
Function
code
Name
Description
Setting range
Default
P11.02
Frequency
decreasing velocity
of instantaneous
power loss
0.00Hz/s
–P00.03Hz/s (Max.
frequency)
0.00
–P00.03
1.00Hz/s
After the power loss of the grid, when the bus voltage drops to the instantaneous power loss
frequency-decreasing point, the VFD begins to decrease the running frequency according to the
decreasing velocity and make the motor in power generation again. The feedback power can maintain
the bus voltage to ensure the continuous running of the VFD until the recovery of power.
Voltage class
660V
1140V
2300V
3300V
Frequency-decreasing
point of instantaneous
power loss
700V
1350V
2700V
3900V
Note:
1. Adjusting the parameter properly can prevent the stop caused by the VFD protection during shifting the
grid.