Goodrive3000 series medium voltage VFD Goodrive3000 inverter
-146-
Function
code
Name
Description
Setting range
Default
communication feedback
6: Ethernet communication feedback
7: Reserved
Select PID feedback channel by the parameter.
Note:
The reference channel and feedback channel cannot coincide; otherwise, PID cannot control
effectively.
2, 3, 5 and 6 can be used only after inserting corresponding extension cards.
Function
code
Name
Description
Setting range
Default
P09.03
PID output feature
0: PID output is positive.
1: PID output is negative.
0
–1
0
Select PID output feature.
0: PID output is positive. When the feedback signal exceeds the PID reference, the output frequency of
the VFD will decrease to balance PID. For example, rewind the strain PID control.
1: PID output is negative. When the feedback signal exceeds the PID reference, the output frequency of
the VFD will increase to balance PID. For example, unwind the strain PID control.
Function
code
Name
Description
Setting range
Default
P09.04
Proportional gain
(Kp)
0.00
–100.00
0.00
–100.00
1.00
The function is applicable to the proportional gain P of PID input.
P determines the strength of the whole PID adjuster. Larger P, stronger the adjustment. The parameter of
100 means that when the offset of PID feedback and reference value is 100%, the adjusting range of PID
adjuster is the maximum frequency (ignoring integral and differential function).
Function
code
Name
Description
Setting range
Default
P09.05
Integral time(Ti)
0.00
–10.00s
0.00
–10.00
0.10s
This parameter determines the speed of the integral adjustment on the deviation of PID feedback and