Goodrive3000 series medium voltage VFD Goodrive3000 PWM rectifier
-72-
Function
code
Name
Description
Setting
range
Default Modify
P10.45
IGBT temperature
at 2nd-last fault
-20.0
–120.0°C
-20.0
–120.0
0.0°C
●
P10.46
Reserved
●
P10.47
Reserved
●
P10.48
Reserved
●
P10.49
Reserved
●
P10.50
Reserved
●
P10.51
Reserved
●
P10.52
Reserved
●
P10.53
Reserved
●
P11 group
––Serial communication and CANopen communication
P11.00
Local
communication
address
1
–247
0: Broadcast address
1
–247
1
○
P11.01
Baud rate setting
0: 1200BPS
1: 2400BPS
2: 4800BPS
3: 9600BPS
4: 19200BPS
5: 38400BPS
0
–5
4
○
P11.02
Check bit setting
0: No check (N, 8, 1)for RTU
1: Even check (E, 8, 1) for RTU
2: Odd check (O, 8, 1) for RTU
3: No check (N, 8, 2) for RTU
4: Even check (E, 8, 2) for RTU
5: Odd check (O, 8, 2) for RTU
0
–5
1
○
P11.03
Response delay
0
–200ms
0
–200
5
○
P11.04
Communication
overtime fault
0.0 (invalid), 0.1
–60.0s
0.0
–60.0s
0.0s
○
P11.05
Transmission error
processing
0: Report fault and coast to
stop
0
–3
0
◎