Goodrive3000 series medium voltage VFD Goodrive3000 PWM rectifier
-38-
Function
code
Name
Description
Setting range
Default
P06.18
Upper limit
corresponding AO1
output
-10.00V
–10.00V
-10.00V
–10.00V
10.00V
P06.19
AO1 output filtering
time
0.000
–10.000s
0.000
–10.000s
0.000s
P06.20
Lower output limit 2 -100.0%
–P06.22
-100.0%
–P06.22
0.0%
P06.21
Lower limit
corresponding AO2
output
-10.00
–10.00V
-10.00
–10.00V
0.00V
P06.22
Upper output limit 2 P06.20
–100.0%
P06.20
–100.0%
100.0%
P06.23
Upper limit
corresponding AO2
output
-10.00V
–10.00V
-10.00V
–10.00V
10.00V
P06.24
AO2 output filtering
time
0.000
–10.000s
0.000
–10.000s
0.000s
The function code defines the relationship between the output value and analog output. When the output
exceeds the range, it will be calculated at the upper limit or lower limit value.
If the analog output is the current output, the function of 1mA is the same as the function of 0.5V.
In different applications, 100% of the output value corresponds to different analog output.
-100%
100%
Corresponding
setting
AO
-10V
10V
(20mA)
0
AO1, AO2
(-20mA )