Goodrive3000 series medium voltage VFD Goodrive3000 inverter
-140-
Function
code
Name
Description
Setting range
Default
P08.38
Threshold voltage of
energy braking
600.0
–6000.0V
600.0
–6000.0
1950.0V
After setting the original bus voltage for the energy braking, adjust this parameter appropriately to
achieve effective load braking. The default value changes with different voltage grades.
Function
code
Name
Description
Setting range
Default
P08.39
Running mode of
cooling fan
0: Normal running mode
1: The fan keeps running after power
on all the time.
0
–1
0
The function code is used to set the running mode of the cooling fan.
0: Normal running mode: the cooling fan runs when the rectifier receives the running command or the
module detection temperature reaches above 45°C or the the module current exceeds 20% rated value.
1: The fan keeps running after power on all the time. (The mode is generally applied to high temperature
and humidity situations, but in other cases it is not recommended.)
Function
code
Name
Description
Setting range
Default
P08.41
Over modulation
selection
0: Invalid
1: Valid
0
–1
0x01
The function code is used to enable the over modulation function.
Function
code
Name
Description
Setting range
Default
P08.42
Keypad data control
0x0000
–0x1223
LED ones: Frequency enabling
selection
0: Both
∧
/
∨
and digital
potentiometer adjustments are
effective.
1: Only
∧
/
∨
is effective.
2: Only digital potentiometer
adjustment is effective.
3: Neither
∧
/
∨
nor digital
potentiometer adjustments is
0000
–1223
0x0000