Goodrive3000 series medium voltage VFD PROFIBUS communication
-292-
Function
code
Name
Description
Setting range Default
P15.13
Sent PZD2
0: Invalid
1: Running frequency (*100, Hz)
2: Set frequency (*100, Hz)
3: Bus voltage (*10, V)
4: Output voltage (*1, V)
5: Output current (*10, A)
6: Output torque actual value (*10, %)
7: Output power actual value (*10, %)
8: Rotating speed during running (*1,
RPM)
9: Running linear speed (*1, m/s)
10: Ramp reference frequency
11: Fault code
12: AI1 value (*100, V)
13: AI2 value (*100, V)
14: AI3 value (*100, V)
15: PULSE frequency (*100, kHz)
16: Terminal input state
17: Terminal output state
18: PID reference (*100, %)
19: PID feedback (*100, %)
20: Motor rated torque
0
–20
0
P15.14
Sent PZD3
0
–20
0
P15.15
Sent PZD4
0
–20
0
P15.16
Sent PZD5
0
–20
0
P15.17
Sent PZD6
0
–20
0
P15.18
Sent PZD7
0
–20
0
P15.19
Sent PZD8
0
–20
0
P15.20
Sent PZD9
0
–20
0
P15.21
Sent PZD10
0
–20
0
P15.22
Sent PZD11
0
–20
0
P15.23
Sent PZD12
0
–20
0
P15.24
Temporary variable 1 for
PZD sending
0
–65535
0
–65535
0
P15.25
DP communication
timeout fault duration
0.1
–60.0s
0.0: Invalid
0.0
–60.0
0.0s
P15.26
CAN communication
timeout fault duration
0.1
–60.0s
0.0: Invalid
0.0
–60.0
0.0s
P15.27
CANopen
communication baud rate
0: 1000k
1: 800k
2: 500k
3: 250k
0
–7
0