Goodrive3000 series medium voltage VFD Goodrive3000 inverter
-100-
P04 group
––V/F control
Function
code
Name
Description
Setting range
Default
P04.00
Motor 1 V/F curve
setting
0: Straight line V/F curve
1: Multi-dot V/F curve
2: Torque step-down V/F curve
(power of 1.3)
3: Torque step-down V/F curve
(power of 1.7)
4: Torque step-down V/F curve
(power of 2.0)
5: Customized V/F curve (V/F
separation)
0
–5
0
These function codes define the V/F curves of Goodrive3000 series motor 1 to meet different
requirements of load features.
0: Straight line V/F curve: suitable for constant torque load
1: Multi-dot V/F curve
2: Torque step-down V/F curve (power of 1.3)
3: Torque step-down V/F curve (power of 1.7)
4: Torque step-down V/F curve (power of 2.0)
Curves 2
–4 are suitable for variable torque load such as fans and water pumps. Users can adjust
according to load features to achieve the most effective energy saving.
5: Customized V/F curve (V/F separation)
V and F separate in the mode. The feature of the curve changes either by the frequency channel of
P00.06 adjusting F or by the voltage channel of P04.27 adjusting V.
Note:
In the following figure, V
b
is motor rated voltage and f
b
is motor rated frequency.
Output voltage
Output frequency
Linear type
Square type
Torque step-down V/F curve (1.3
th
order)
Torque step-down V/F curve (1.7
th
order)
Torque step-down V/F curve (2.0
nd
order)
Function
code
Name
Description
Setting range
Default
P04.01
Motor 1 torque boost 0.0%: (Automatic) 0.1%
–10.0%
0.0
–10.0
0.0%
P04.02
Motor 1 torque boost
close
0.0%
–50.0% (Relative to motor 1
rated frequency )
0.0
–50.0
20.0%
Boost and compensate the output voltage for the features of low frequency torque. P04.01 is on the basis