Goodrive3000 series medium voltage VFD Goodrive3000 inverter
-78-
0: Keypad running command channel("LOCAL/REMOT" light off)
Carry out the command control by RUN, STOP/RST on the keypad.
Press RUN and STOP/RST simultaneously in running state to make the VFD coast to stop.
1: Terminal running command channel ("LOCAL/REMOT" flickering)
Carry out the running command control by the forward rotation, reverse rotation and forward jogging and
reverse jogging of the multi-function terminals
2: Communication running command channel ("LOCAL/REMOT" on);
The running command is controlled by the upper computer via communication.
Function
code
Name
Description
Setting range
Default
P00.02
Communication
running commands
0:MODBUS communication channel
1: PROFIBUS/CANopen
communication channel
2:Ethernet communication channel
3:Reserved
0
–3
0
Select the controlling communication command channel of the VFD.
Note: 1 and 2 are extension functions which need corresponding extension cards.
Function
code
Name
Description
Setting range
Default
P00.03
Max. output
frequency
P00.04
–400.00Hz
P00.04
–400.00
50.00Hz
Users should pay attention that the parameter used to set the maximum output frequency is the basis of
frequency setting, acceleration and deceleration.
Function
code
Name
Description
Setting range
Default
P00.04
Upper limit of
running frequency
P00.05
– P00.03(Max. frequency)
P00.05
–P00.03
50.0Hz
The upper limit of running frequency is the upper limit of output frequency of the VFD which is lower than
or equal to the maximum output frequency.
If the set frequency is above the upper limit, the VFD runs at the upper limit.
Function
code
Name
Description
Setting range
Default
P00.05
Lower limit of
0.00Hz
–P00.04 (Upper limit of
0.00
–P00.04
0.00 Hz