![INVT GD200L-004G-4 Скачать руководство пользователя страница 94](http://html1.mh-extra.com/html/invt/gd200l-004g-4/gd200l-004g-4_operation-manual_2085737094.webp)
Goodrive200L
inverters Function parameters
89
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
pre-alarm and the inverter stops running after
overload fault
2: The inverter continues to work after overload
pre-alarm and the inverter stops running after
underload fault
3. The inverter stops when overloading or
underloading.
LED hundreds :
0:Detection all the time
1:Detection in constant running
Setting range of P11.09: P11.11~200%
Setting range of P11.10: 0.1~3600.0s
P11.11
Detection
level of the
underload
pre-alarm
If the inverter current or the output current is
lower than P11.11, and its lasting time is beyond
P11.12, the inverter will output underload
pre-alarm.
Setting range of P11.11: 0~P11.09
Setting range of P11.12: 0.1~3600.0s
50%
○
P11.12
Detection
time of the
underload
pre-alarm
1.0s
○
P11.13
Output
terminal
action during
fault
Select the action of fault output terminals on
undervoltage and fault reset.
0x00~0x11
LED ones:
0:Action under fault undervoltage
1:No action under fault undervoltage
LED tens:
0:Action during the automatic reset
1:No action during the automatic reset
0x00
○
P11.16
Extension
functions
selection
0x00~0x11
LED ones:Voltage drop frequency-decreasing
selection
0: Voltage drop frequency-decreasing selection
disable
1: Voltage drop frequency-decreasing selection
enable
LED tens: Step 2 ACC/DEC time option
0:
Step 2
ACC/DEC time option
disable
1: Step 2 ACC/DEC time option enable
,
when
running frequency more than P08.36, ACC/DEC
time switch to step 2 ACC/DEC time
00
○
P13 Group Reserved
Содержание GD200L-004G-4
Страница 1: ...Goodrive 200L...
Страница 139: ...Goodrive200L inverters Fault tracking 134 8 6 2 Motor vibration 8 6 3 Overvoltage...
Страница 140: ...Goodrive200L inverters Fault tracking 135 8 6 4 Undervoltage fault 8 6 5 Abnormal motor heat...
Страница 141: ...Goodrive200L inverters Fault tracking 136 8 6 6 Inverter overheating 8 6 7 Stall during the acceleration of the motor...
Страница 187: ...201606 V1 0...