Goodrive200L
inverters Basic operation instruction
122
The function code which can improve the elevator comfort of stopping is showed as follow:
P08.02: The start time of S-curve stopping setting
P08.03: The arrival time of S-curve stopping setting
P00.12: Deceleration time;
P03.00: ASR speed proportion gain 1
P03.01: ASR speed integral time 1
11.
Emergency running function
Function
Code
Name
Description
Range
Modify
Factory
setting
P01.30
The control
selection of
emergency
running
direction
0:External controller
1:Inverter
0~1
○
0
P01.31
Emergency
running
frequency
0.00Hz~P00.03(max
frequency)
0.00~P00.03
○
5.00Hz
P06.01
Y output
selection
0:Without output
1:Running
2: Forward rotation
3: Reversal rotation
5:Inverter fault
6:The detection of
frequency level FDT1
7:The detection of
frequency level FDT2
14:Overload
forewarning
27: Under the
emergency running
state, require to
change the direction
of motor. (P01.30 is
valid)
29: SPI fault detection
output
0~30
○
27
P06.02
HDO output
selection
0~30
○
0
P06.03
RO1relay
output
selection
0~30
○
1(Output
connects
to the
running
contactor.)
P06.04
RO2 relay
output
selection
0~30
○
6(Output
connects
to the
braking
contactor.)
It can support single phase UPS or ARD for emergency running. The configuration of the
UPS or ARD is 1PH 220VAC or 3PH 380VAC. The detection of the losing phase and under
voltage parameters are no need to be changed.
In emergency running mode, there are two way for changing the running direction of elevator
by setting the parameter of P01.30.
a.
When the inverter can’t actuate the motor, inverter will output the signal to the
Содержание GD200L-004G-4
Страница 1: ...Goodrive 200L...
Страница 139: ...Goodrive200L inverters Fault tracking 134 8 6 2 Motor vibration 8 6 3 Overvoltage...
Страница 140: ...Goodrive200L inverters Fault tracking 135 8 6 4 Undervoltage fault 8 6 5 Abnormal motor heat...
Страница 141: ...Goodrive200L inverters Fault tracking 136 8 6 6 Inverter overheating 8 6 7 Stall during the acceleration of the motor...
Страница 187: ...201606 V1 0...