Goodrive200L
inverters Function parameters
66
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
device which is 18.5kW or higer than 18.5 kW)
BIT8:analog AI2 value(V on)
BIT9: analog AI3 value(V on)
BIT10:high speed pulse HDI frequency
BIT11:PLC and the current step in multi-step
speed
BIT12:pulse counters
BIT13:length value
BIT14: upper limit frequency (Hz on)
P07.08
Frequency
coefficient
0.01~10.00
Displayed frequency=running frequency* P07.08
1.00
○
P07.09
Rotation
speed
coefficient
0.1~999.9%
Mechanical rotation speed =120*displayed
running frequency×P07.09/motor pole pairs
100.0%
○
P07.10
Linear speed
coefficient
0.1~999.9%
Linear speed= Mechanical rotation
speed×P07.10
1.0%
○
P07.11
Rectifier
bridge
module
temperature
0~100.0
℃
●
P07.12
Converter
module
temperature
0~100.0
℃
●
P07.13
Software
version
1.00~655.35
●
P07.14
Local
accumulative
running time
0~65535h
●
P07.15
High bit of
power
consumption
Display the power used by the inverter.
The power consumption of the inverter
=P07.15*1000+P07.16
Setting range of P07.15: 0~65535°(*1000)
Setting range of P07.16: 0.0~999.9°
●
P07.16
Low bit of
power
consumption
●
P07.17 Inverter type
0: G type
1: P type
●
P07.18
The rated
power of the
inverter
0.4~3000.0kW
●
Содержание GD200L-004G-4
Страница 1: ...Goodrive 200L...
Страница 139: ...Goodrive200L inverters Fault tracking 134 8 6 2 Motor vibration 8 6 3 Overvoltage...
Страница 140: ...Goodrive200L inverters Fault tracking 135 8 6 4 Undervoltage fault 8 6 5 Abnormal motor heat...
Страница 141: ...Goodrive200L inverters Fault tracking 136 8 6 6 Inverter overheating 8 6 7 Stall during the acceleration of the motor...
Страница 187: ...201606 V1 0...