Goodrive200L
inverters Fault tracking
130
Fault
code
Fault type
Possible cause
What to do
STo
Maladjustment fault
The control
parameters of the
synchronous motors
not set properly
The autoturn
parameter is not right
The inverter is not
connected to the
motor
Check the load and
ensure it is normal
Check whether the
control parameter is
set properly or not
Increase the
maladjustment
detection time
END
Time reach of factory
setting
The actual running
time of the inverter is
above the internal
setting running time
Ask for the supplier
and adjust the setting
running time
PCE
Keypad communication
fault
The connection of the
keypad wires is not
good or broken
The keypad wire is too
long and affected by
strong interference
There is circuit fault on
the communication of
the keypad and main
board
Check the keypad
wires and ensure
whether there is
mistake
Check the environment
and avoid the
interference source
Change the hardware
and ask for service
Содержание GD200L-004G-4
Страница 1: ...Goodrive 200L...
Страница 139: ...Goodrive200L inverters Fault tracking 134 8 6 2 Motor vibration 8 6 3 Overvoltage...
Страница 140: ...Goodrive200L inverters Fault tracking 135 8 6 4 Undervoltage fault 8 6 5 Abnormal motor heat...
Страница 141: ...Goodrive200L inverters Fault tracking 136 8 6 6 Inverter overheating 8 6 7 Stall during the acceleration of the motor...
Страница 187: ...201606 V1 0...