![INVT GD200L-004G-4 Скачать руководство пользователя страница 38](http://html1.mh-extra.com/html/invt/gd200l-004g-4/gd200l-004g-4_operation-manual_2085737038.webp)
Goodrive200L
inverters Function parameters
33
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
control when P00.06=7 or P00.07=7. It is
necessary to set P09. The running frequency of
the inverter is the value after PID effect. See P09
for the detailed information of the preset source,
preset value, and feedback source of PID.
8:MODBUS communication setting
The frequency is set by MODBUS
communication. See P14 for detailed information.
9:PROFIBUS/CANopen communication
10:Ethernet communication
11:Reserved
Note:
A frequency and B frequency can not set
as the same frequency reference mode.
P00.08
B frequency
command
reference
0:Maximum output frequency, 100% of
B frequency setting corresponds to the maximum
output frequency
1: A frequency command, 100% of B frequency
setting corresponds to the maximum output
frequency. Select this setting if it needs to adjust
on the base of A frequency command.
0
○
P00.09
Combination
of the setting
source
0: A, the current frequency setting is A frequency
command
1: B, the current frequency setting is B frequency
command
2: A+B, the current frequency setting is A
frequency c B frequency command
3: A-B, the current frequency setting is A
frequency command - B frequency command
4: Max (A, B): the bigger one between A
frequency command and B frequency is the set
frequency.
5: Min (A, B): The lower one between A
frequency command and B frequency is the set
frequency.
Note:
The combination manner can be shifted by
P05(terminal function)
0
○
P00.10
Keypad set
frequency
When A and B frequency commands are selected
as “keypad setting”, this parameter will be the
initial value of inverter reference frequency
Setting range:0.00 Hz~P00.03
(the Max. frequency)
50.00
Hz
○
Содержание GD200L-004G-4
Страница 1: ...Goodrive 200L...
Страница 139: ...Goodrive200L inverters Fault tracking 134 8 6 2 Motor vibration 8 6 3 Overvoltage...
Страница 140: ...Goodrive200L inverters Fault tracking 135 8 6 4 Undervoltage fault 8 6 5 Abnormal motor heat...
Страница 141: ...Goodrive200L inverters Fault tracking 136 8 6 6 Inverter overheating 8 6 7 Stall during the acceleration of the motor...
Страница 187: ...201606 V1 0...