Goodrive200L
inverters Product overview
7
3.3 Product specification
Function
Specification
Input
Input voltage (
V
)
AC 3PH 220V(-15%)~240V(+10%)
AC 3PH 380V(-15%)~440V(+10%)
AC 3PH 520V(-15%)~690V(+10%)
Input current (
A
)
Refer to
the
rated value
Input frequency (
Hz
)
50Hz or 60Hz
Allowed range: 47~63Hz
Output
Output voltage (
V
)
0~Input voltage
Output current (
A
)
Refer to
the rated value
Output power (
kW
)
Refer to
the rated value
Output frequency (
Hz
) 0~400Hz
Technical
control
feature
Control mode
SVPWM, SVC and closed-loop vector control
Motor type
Asynchronous motor
Speed ratio
Asynchronous motor 1:100 (SVC)
Speed control
accuracy
±0.2% (sensorless vector control)
Speed fluctuation
± 0.3%(sensorless vector control)
Torque response
<20ms(sensorless vector control)
Torque control
accuracy
10%(sensorless vector control)
Starting torque
Asynchronous motor: 0.5Hz/150% (SVC)
Overload capability
G type:
150% of rated current: 1 minute
180% of rated current: 10 seconds
200% of rated current: 1 second
Running
control
feature
Frequency setting
Digital setting, analog setting, pulse frequency
setting, multi-step speed running setting, simple
PLC setting, PID setting, MODBUS communication
setting.
Shift between the set combination and set channel.
Auto voltage
adjustment
Keep a stable voltage automatically when the grid
voltage transients
Fault protection
Provide over 30 fault protection functions:
overcurrent, overvoltage, undervoltage, overheating,
phase loss and overload, etc.
Speed tracking
Restart the rotating motor smoothly
Note: This function is available for the inverters of
4kW and above 4kW.
Peripheral
interface
Terminal analog input
resolution
≤ 20mV
Terminal switch input
≤ 2ms
Содержание GD200L-004G-4
Страница 1: ...Goodrive 200L...
Страница 139: ...Goodrive200L inverters Fault tracking 134 8 6 2 Motor vibration 8 6 3 Overvoltage...
Страница 140: ...Goodrive200L inverters Fault tracking 135 8 6 4 Undervoltage fault 8 6 5 Abnormal motor heat...
Страница 141: ...Goodrive200L inverters Fault tracking 136 8 6 6 Inverter overheating 8 6 7 Stall during the acceleration of the motor...
Страница 187: ...201606 V1 0...